Description
OVERVIEW
| Operational mode | Intermittent operation, continuous operation, 72-hour operation without permanent supervision |
| Safety | Self-monitoring and fail-safe |
| Auxiliary supply | 24 VDC |
| Flame relay | 1x NO contact, 230 VAC, 2 A |
| Status relay | 1x NO contact, 230 VAC, 2 A |
| Flame Failure Detection Time (FFDT) | 1, 3, 5 s |
| Flame intensity | 0/4…20 mA |
| Spectral ranges | UV, VIS, IR |
| Number of ranges | 1 |
| Switching threshold | 0…9 |
| Viewing angle | 6° |
| Display | LED display |
| Perm. ambient temperature | -20…+60°C |
| Sighting tube connection | G 1¼” or 1¼” NPT(F) |
| Purge air connection | G ½” or ½” NPT(F) |
| Protection class | IP67 |
| Dimensions | 90 x 92 mm, length approx. 350 mm |
| Weight | approx. 1.8 kg |
TECHNOMASTER IS A CERTIFIED DISTRIBUTOR FOR DURAG IN EGYPT