Description
OVERVIEW
- Suitable for intermittent operation and continuous operation
- Optional parallel operation of two flame sensors in any combination: UV/UV, UV/IR or IR/IR
- Three different settings supported for various modes (e.g. dependent on fuel or combustion technology), automatic activation by burner management system
- Plain text display
APPLICATIONS
- Power stations
- Chemical industry
- Refineries
- Cement plants
- Waste incinerators
- Steam generators
- Heating plants
TECHNICAL DATA
Operation mode | Intermittent operation, continuous operation, 72-hour operation without continual supervision |
Safety | Self-monitoring and fail-safe |
Power supply | 24 VDC, 115/230 VAC |
Protection | IP00 |
Flame relay | 1x switch-over contact, 230 VAC, 2 A |
Status relay | 1x switch-over contact, 230 VAC, 2 A |
Threshold setting | 00…99 |
Safety time | 1 … 5.5 s |
Pre-configurable combinations of switching threshold and safety time | 3 |
Flame sensor connection | 1 or 2 (parallel) |
Display | alpha-numeric LCD display |
Flame intensity | 0/4…20 mA |
Flame signal | 0/4…20 mA |
Perm. ambient temperature | -20…+60°C |
Dimensions | 19” plug-in module, 3 RU, 21 HP |
Weight | approx. 1 kg |